You can change the humidity parameter that is output on the RH channel of HMD62 with the DIP switches on the component board. Select the
parameter you want the transmitter to output by sliding the parameter's DIP switch to the right (ON). In the example in Figure 1, the transmitter's selected output parameter is dew point/frost point temperature
(Tdf). Keep the other DIP switches in the OFF position (left).
The selected parameter uses the default scaling shown in Table 1.
Table 1. HMD62 Default Parameter Scaling
Parameter
Default Scaling for 4 … 20 mA Output Range
RH
0 … 100 %RH
Td
-40 ... +80 °C (-40 ... +176 °F)
Tdf
-40 ... +80 °C (-40 ... +176 °F)
A
0 … 300 g/m3 (0 … 131.1 gr/ft3)
X
0 … 600 g/kg (0 … 4200 gr/lb)
Tw
-40 ... +80 °C (-40 ... +176 °F)
H
-40 … 1600 kJ/kg (-9.5 ... 695.6 Btu/lb)
If you need to change the default scaling of a parameter, configure the output
with Vaisala Insight PC software. See the instructions in HMD60 User Guide.
CAUTION If you use the
Insight software to further configure the output, note that the DIP switch selections override the Insight configuration. When using Insight to configure the output, set all DIP switches to
the OFF position (left) to ensure they do not cause a conflict with the Insight settings.