Available Parameters and Default Scaling - TMD62 - HMD62 - HMD60

HMD62 TMD62 User Guide

Document code
M212016EN
Revision
C
Language
English (United States)
Product
TMD62
HMD62
HMD60
Document type
User guide

HMD62 Measurement Parameters and Default Analog Output Scaling

Table 1 shows the available output parameters and the default analog output scaling of the parameters for HMD62.

Table 1. HMD62 Measurement Parameters and Default Scaling
Parameter Default Scaling for 4 … 20 mA Output Range
Relative humidity (RH) 0 … 100 %RH
Temperature (T) -20 ... +80 °C (-4 ... +176 °F)
Dew point temperature (Td) -40 ... +80 °C (-40 ... +176 °F)
Dew point/frost point temperature (Tdf) -40 ... +80 °C (-40 ... +176 °F)
Absolute humidity (A) 0 … 300 g/m3 (0 … 131.1 gr/ft3)
Mixing ratio (X) 0 … 600 g/kg (0 … 4200 gr/lb)
Wet-bulb temperature (Tw) -40 ... +80 °C (-40 ... +176 °F)
Enthalpy (H) -40 … 1600 kJ/kg (-9.5 ... 695.6 Btu/lb)

TMD62 Measurement Parameters and Default Analog Scaling

Table 2 shows the available output parameters and the default analog output scaling of the parameters for TMD62.

Table 2. TMD62 Measurement Parameters and Default Scaling
Parameter Default Scaling for 4 … 20 mA Output Range
Temperature (T) -20 ... +80 °C (-4 ... +176 °F)

Changing Measurement Parameter Scaling

If your application requires an analog output scaling that differs from the defaults shown in Table 1 and Table 2, you can configure the scaling by connecting the transmitter to Vaisala Insight PC software (requires Vaisala USB cable 219690).