Setting Filtering Factor with Insight - SWINSIGHT10 - TMD62 - HMD62 - HMD60

HMD62 TMD62 User Guide

Document code
M212016EN
Revision
C
Language
English (United States)
Product
TMD62
HMD62
HMD60
Document type
User guide
Figure 1. Filtering Factor Configuration View (HMD62 Example)
1
Enable filtering by moving the slider to the right (ON)
To set a filtering factor for the transmitter's measurement output:
  1. Select > Configure Device > Filtering.
  2. Enable filtering with the ON/OFF selections (slide right to enable, left to disable).
  3. Enter a filtering factor below 1.000 to apply filtering to the output (range: 0.001 … 1.000).
    Examples of the effect of filtering on output:
    • Filtering factor 1.000 = No filtering, the latest measurement is output directly without integrating previous measurements.
    • Filtering factor 0.500 = The reading output integrates 50% of the previous measurement with the latest measurement.
    • Filtering factor 0.100 = The reading output integrates 90% of the previous measurement with the latest measurement.
  4. Select Save when done and exit with Close.