Modbus registers - HPP272

HPP272 User Guide

Document code
M211972EN
Revision
G
Language
English
Product
HPP272
Document type
User guide

Registers are numbered in decimal, starting from 1. Register addresses in actual Modbus messages (Modbus Protocol Data Unit (PDU)) are in hexadecimal and start from zero. Register number 1 corresponds to address 0hex in the actual Modbus message.

CAUTION

Reading the wrong register(s) may result in correct-looking values. Check the reference documentation of your Modbus host (PLC) to verify which notation it uses for Modbus register addresses.