- 1
- Output Mode: Select whether the relay activates above or below a set trigger value (or set the relay Off).
- 2
- Parameter: The measurement that is used to control the relay.
- 3
- Unit: Select the unit of the measurement parameter that controls the relay (for example, % if the measurement is in %CO2).
- 4
- Low Trigger Level and High Trigger
Level: If you want to activate the relay above or below a single
setpoint without using hysteresis, enter the same value for the low trigger and the
high trigger. The Output Mode selection defines whether the
relay activates above or below this value.
If you want to set a hysteresis, define the limits of the hysteresis with the low and high triggers. See the Indigo documentation for instructions on setting a hysteresis.
- 5
- Error State: Select which state the relay is set to when an error occurs (on, off, or remains in its current state)
For detailed instructions on configuring relays with Indigo, see the Indigo transmitter's User Guide. |