Property | Specification |
---|---|
Analog outputs |
3 voltage (V) or current (mA) outputs:
|
Accuracy of analog outputs at +20 °C (+68 °F) | ± 0.1 % full scale |
Relays | 2 configurable relays (VAC/VDC) |
Device maximum specification (resistive load):
|
|
UL-rated maximum specification (resistive load):
|
|
Power supply input 1 |
15 ... 30 VDC (24VAC +/- 10 % 50/60Hz) |
Maximum current | Transmitter and connected probe max. 1 A |
Power consumption | Transmitter max. 3 W (+ connected probe, varies depending on probe type) |
Probe connector | M12/5 connector for probe or probe cable connection (Vaisala Indigo-compatible probes) |
Cable lead-throughs | 2 options: rubber lead-through on the bottom of the transmitter, and opening with a seal at the back of the transmitter |
Screw terminal wire size | 0.2 ... 1.5 mm2 |
Depending on the production date of your transmitter, the power supply input voltage specification can be either 15 ... 30 VDC (20 ... 22 VAC) or 15 … 30 VDC (24VAC +/- 10 % 50/60Hz). Check the type label on the back of the transmitter for information specific to your device. |
CAUTION Do not modify the unit or use it in ways not described in the documentation. Improper modification may lead to safety hazards, equipment damage, failure to perform according to specification, or decreased equipment lifetime. |
1 Using a power supply with overload protection is recommended for electrical
safety.