Setting Relay Activation Limit Without Hysteresis - INDIGO200SERIES - INDIGO201

Indigo 201 User Guide

Document code
M211877EN
Revision
F
Language
English (United States)
Product
INDIGO200SERIES
INDIGO201
Document type
User guide
You can set the relay to activate when the probe measurement exceeds or falls below a set limit. When you configure a single setpoint for relay activation without hysteresis, the relay switches on or off immediately when the measurement moves over or below the setpoint (depending on the low/high activation mode selection).
When you enter a value into a field, the value is saved automatically when you exit the input field (for example, tap on an area outside of the field).
To define a single setpoint for relay activation:
  1. Open the Settings > Relays menu in the wireless configuration interface.
  2. In the Relays menu, select the relay activation mode from the Output Mode dropdown menu:
    1. Select Active above trigger level if you want the relay to activate when the probe measurement exceeds the set limit
    2. Select Active below trigger level if you want the relay to activate when the probe measurement falls below the set limit
  3. Select the measurement parameter that is used to control the relay with the Parameter dropdown.
  4. Set the unit of the measurement parameter with the Unit dropdown.
  5. Enter the same measurement limit to both the Low Trigger Level and the High Trigger Level field.
    With this configuration, there is no hysteresis. The relay activates or switches off immediately after passing this point.
  6. Select the Error State for the relay.