Read the known test values from the test registers to verify the functionality of your Modbus implementation.
Register number | Address | Data format | Test value |
---|---|---|---|
201 | 00C8hex | 16-bit unsigned integer | 12345 |
202 | 00C9hex | 32-bit unsigned integer | 1234567890 |
00CAhex | |||
204 | 00CBhex | 64-bit unsigned integer | 1234567890123456789 |
00CChex | |||
00CDhex | |||
00CEhex | |||
208 | 00CFhex | 16-bit integer | -12345 |
209 | 00D0hex | 32-bit integer | -1234567890 |
00D1hex | |||
211 | 00D2hex | 64-bit integer | -1234567890123456789 |
00D3hex | |||
00D4hex | |||
00D5hex | |||
215 | 00D6hex | 32-bit float | 1.23456 |
00D7hex | |||
217 | 00D8hex | 64-bit float | 1.23456789 |
00D9hex | |||
00DAhex | |||
00DBhex |