Configuring Modbus protocol - OPT100

OPT100 User Guide

Document code
M211858EN
Revision
V
Language
English
Product
OPT100
Document type
User guide
Figure 1. Modbus settings page
  1. Connect to the user interface as the Admin user.
  2. In the user interface, select Settings > Network > Modbus.
  3. Select the connection type(s) for which Modbus protocol should be enabled. Select TCP (Ethernet), RTU (serial line), or both.
  4. If you enabled Modbus RTU, configure the serial connection:
    1. Select Baud rate for the connection. Available options are:
      • 4800
      • 9600
      • 19200
      • 38400
      • 57600
      • 115200
    2. Select Transmission mode, 8E1 or 8N2.
    3. Enter the Modbus Slave ID for the DGA monitor. Range 1 ... 247.
  5. Click Apply to save your changes.