Parameter 1 | Range | Accuracy 2 3 | Repeatability 3 |
---|---|---|---|
Methane (CH4) | 0–10 000 ppmv | ±4 ppm or ±5 % of reading | 10 ppm or 5 % of reading |
Ethane (C2H6) | 0–10 000 ppmv | ±10 ppm or ±5 % of reading | 10 ppm or 5 % of reading 4 |
Ethylene (C2H4) | 0–10 000 ppmv | ±4 ppm or ±5 % of reading | 10 ppm or 5 % of reading |
Acetylene (C2H2) | 0–5000 ppmv | ±0.5 ppm or ±5 % of reading | 1 ppm or 5 % of reading |
Carbon monoxide (CO) | 0–10 000 ppmv | ±4 ppm or ±5 % of reading | 10 ppm or 5 % of reading |
Carbon dioxide (CO2) | 0–10 000 ppmv | ±4 ppm or ±5 % of reading | 10 ppm or 5 % of reading |
Hydrogen (H2) | 0–5000 ppmv | ±15 ppm or ±10 % of reading | 15 ppm or 10 % of reading |
Moisture 5 (H2O) | 0–100 ppmw 6 | ±2 ppm 7 or ±10 % of reading | Included in accuracy |
Total gas pressure | 0–2000 hPa | ±10 hPa or ±2 % of reading | 10 hPa or 5 % of reading |
Property | Description/Value |
---|---|
Measurement cycle duration | 1–1.5 h (typical) |
Response time (T63) | One measurement cycle 8 |
Warm-up time until first measurement data available | Two measurement cycles |
Initialization time to full accuracy | Two days |
Data storage | At least 10 years 9 |
Expected operating life | > 15 years |
Parameter | Typical variance to laboratory DGA10 11 |
---|---|
Acetylene (C2H2) | ±1 ppm or ±10 % of reading |
Hydrogen (H2) | ±15 ppm or ±15 % of reading |
Other measured gases | ±10 ppm or ±10 % of reading |
Moisture (H2O) | ±2 ppm or ±10 % of reading |
Property | Description/Value |
---|---|
Total dissolved combustible gases (TDCG) | Combined total of H2, CO, CH4, C2H6, C2H4, and C2H2 |
24 h average | Available for single gases, moisture, TDCG, and total gas pressure |
Rate of change (ROC) | Available for single gases and TDCG for 24 h, 7 d, and 30 d periods |
Gas ratios 12 |
Available ratios:
|
Property | Description/Value |
---|---|
Transformer liquid type 13 | Mineral oil or ester liquids |
Required minimum fire point of insulation liquid 14 | +125 °C (+257 °F) |
Transformer oil pressure at oil inlet |
Max. 2 bar (absolute) continuous Burst pressure 20 bar (absolute) |
Transformer insulation liquid temperature at oil inlet |
Max. +100 °C (+212 °F) Min. +0 °C (+32 °F) for ester liquids Min. temperature for mineral oil depends on the pour point of the mineral oil. |
Ambient humidity range | 0–100 %RH, condensing |
Ambient temperature range in operation | −40 … +55 °C (−40 … +131 °F) |
Storage temperature range | −40 … +60 °C (−40 … +140 °F) |
IP rating |
IP66: Dust-tight. Protected from powerful water jets from any direction. |
Property | Description/Value |
---|---|
Operating voltage |
OPTPSU1: 100–240 V AC, 50–60 Hz, ±10 % OPTPSU2: 110–220 V DC, ±10 % |
Overvoltage category | III |
Maximum power consumption | 500 W |
Typical power consumption at +25 °C (+77 °F) | 100 W |
Connector |
Screw terminals (inside power supply unit) Wire size 2.5–4 mm2 (14–12 AWG) |
Property | Description/Value |
---|---|
RS-485 interface | |
Connector |
Screw terminals (inside OPT100 housing) Wire size 0.5–4 mm2 (20–12 AWG) |
Supported protocols | Modbus RTU, DNP3 (optional feature) |
Galvanic isolation | 2 kV RMS, 1 min |
Ethernet interface | |
Connector | Industrial RJ45 connector with protective plug (outside OPT100 housing) |
Supported protocols | Modbus TCP, HTTP, HTTPS, DNP3 (optional feature), IEC 61850 (optional feature) |
Standard | IEEE 802.3 |
Physical layer | Base-T |
Data rate | 10/100 Mbps |
Galvanic isolation | 4 kV AC (50 Hz, 1 min) |
Insulation voltage | 250 Vrms |
Relay outputs | |
Number of relays | 3 pcs, normally open (NO) or normally closed (NC), user‑ selectable |
Trigger type | Gas alert with user‑selectable limits |
Connector |
Screw terminals (inside power supply unit housing) Wire size 0.5–4 mm2 (20–12 AWG) |
Max. switching current |
6 A (at 250 V AC) 2 A (at 24 V DC) 0.2 A (at 250 V DC) |
Min. switching voltage | 12 V DC (at 10 mA) |
Min. switching current | 10 mA (at 12 V) |
Contact type | 1 PDT |
Auxiliary device interface | |
Maximum power | 48 W |
Voltage output | 24 V DC |
User interface | |
Interface type | Web‑based user interface, can be operated with standard web browsers |
Connector for service use | RJ45 connector, inside OPT100 housing (temporary local use only) |
Property | Description/Value |
---|---|
Oil fitting |
Stainless steel Swagelok® fitting for 10 mm (0.39 in) outer diameter tubing. See list of available accessories for adapters. |
Max. length of oil pipe to transformer for mineral oil |
Max. 10 m (33 ft) with 7 mm (0.28 in) inner diameter tubing 15 Max. 5 m (16 ft) with 4 mm (0.15 in) inner diameter tubing |
Max. length of pipe to transformer for ester liquid | Max. 10 m (33 ft) with 8 mm (0.31 in) inner diameter tubing |
Recommended oil pipe properties |
10 mm (0.39 in) outer diameter 1–1.5 mm wall thickness (mineral oil devices) 1 mm wall thickness (ester liquid devices) Material stainless steel |
Dimensions (H × W × D) | |
Installed with ground mounting set and weather shield | 1630 × 675 × 453 mm (64 × 27 × 18 in) |
Installed with wall mounting set and weather shield | 1390 × 675 × 467 mm (55 × 27 × 18 in) |
Installed with antivibration wall mounting set and weather shield | 1395 × 683 × 541 mm (55 × 27 × 21 in) |
Weight | |
OPT100 DGA Monitor | 35 kg (77 lb) |
OPTPSU Power Supply Unit | 12 kg (27 lb) |
OPTMSET1 Wall Mounting Set | 8 kg (18 lb) |
OPTMSET2 Ground Mounting Set | 16 kg (35 lb) |
OPTMSET3 Antivibration Wall Mounting Set | 9 kg (20 lb) |
OPTSHLD1 Weather shield | 6 kg (13 lb) |
Materials | |
OPT100 DGA Monitor housing | Marine aluminum (EN AW-5754), stainless steel AISI 316 |
OPTPSU Power Supply Unit housing | Stainless steel |
OPTMSET1 Wall Mounting Set | Stainless steel AISI 316 |
OPTMSET2 Ground Mounting Set | Stainless steel |
OPTMSET3 Antivibration Wall Mounting Set | Stainless steel |
OPTSHLD1 Weather Shield | Marine aluminum (EN AW-5754) |
Materials in contact with oil | |
Oil pipes, chambers, and valves | Aluminum (EN AW 6026), stainless steel AISI 316, brass |
Gaskets and seals | NBR, FKM, FVMQ |
Pump gears and bushing | PEEK/PTFE |
Property | Description/Value |
---|---|
EU directives and regulations |
EMC Directive (2014/30/EU) Low Voltage Directive (2014/35/EU) |
OPT100 is specifically designed to be installed as part of another type of equipment that is excluded from the RoHS directive (2011/65/EU) scope. |
|
EMC immunity |
EN 61326‑1, industrial environment IEC 61000-6-5, class 4 |
EMC emissions |
FCC 47 CFR 15, section 15.107, class A ISED ICES-003, section 5(a)(i), class A |
Safety |
IEC/EN/UL/CSA‑C22.2 61010‑1 |
Environmental |
IEC 60068‑2‑1 IEC 60068‑2‑2 ISO 6270-1:2017, constant humidity condensation atmosphere, C5 ISO 9227:2017, salt fog, C5 IEC 61010-1:2010/AMD1:2016, pollution degree 4 (outdoor), 3 (industrial area), 2 (device internal) |
Compliance marks |
CE, China RoHS, EAC, RCM |