The DGA monitor can accumulate excess gases in the measurement system. This can happen, for example, because of an air leak in the oil lines. The DGA monitor detects excess gases and enables device alert code 2300, Excess gas in the system.
To restore normal operation, perform the procedure below to bleed the excess gas, and restart measurement after successfully bleeding the system. You must be on site with access to the DGA monitor cabinet, as you have to remove and reattach the bleed plug as instructed.
CAUTION Do not use this procedure for bleeding oil lines. This procedure only works for excess gas inside the DGA monitor. Using this procedure for oil lines may push the air into the transformer and damage it. If the oil lines need bleeding, use forced uninstallation and then perform installation as instructed in OPT100 Installation Guide (M211857EN). |