Supervisor data message (aR5) - WXT530

WXT530 Series User Guide

Document code
M211840EN
Revision
F
Language
English (United States)
Product
WXT530
Document type
User guide

This command requests a supervisor data message containing self-check parameters of the heating system and power supply voltage.

Command format:

aR5<cr><lf>
a Device address
R5 Supervisor message query command
<cr><lf> Command terminator

Example of the response (the parameter set is configurable):

0R5,Th=25.9C,Vh=12.0N,Vs=15.2V,Vr=3.475V,Id=HEL___<cr><lf>
a Device address
R5 Supervisor message query command
Th Heating temperature (C = °C)
Vh Heating voltage (N = heating is off)
Vs Supply voltage (V = V)
Vr 3.5 V reference voltage (V = V)
<cr><lf> Response terminator
Id Information field

The content of the parameter Id is a text string which you can modify with the Vaisala Configuration Tool. The field can include customer-specific, additional information. For more information on changing the settings, see the Vaisala Configuration Tool online help for the Info field in the Device Settings window.