Solving typical problems - GMW83 - GMW83A - GMW83D - GMW83DRP - GMW83DRPC - GMW83RPC - GMW84 - GMW84S - GMW86P - GMW87M

GMW80 Series User Guide

Document code
M211748EN
Revision
H
Language
English
Product
GMW83
GMW83A
GMW83D
GMW83DRP
GMW83DRPC
GMW83RPC
GMW84
GMW84S
GMW86P
GMW87M
Document type
User guide

If you experience problems with GMW80 series transmitters, first see the following tables (for analog output and Modbus models) concerning the behavior and error indications of the transmitter. If you cannot locate the source of the error and return the transmitter to operational state, contact Vaisala. See Technical support.

Table 1. Troubleshooting table, transmitters with analog output
Problem or message Possible cause Solution
Analog output reading is unchanging and appears incorrect. Transmitter has set the analog output to the error level (3.6 mA or 11 V) because the transmitter is in the error state.

Determine what has caused the error state and remove the cause.

For a description of the error state and its possible causes, see Error state.

Temperature reading is too high. Transmitter is installed in an unsuitable location, for example, near a heat source or in sunlight. Relocate transmitter. See Selecting location.
Transmitter is installed in improper orientation. Reinstall transmitter with the arrow on the mounting base pointing up.
Unsuitable operating environment. Verify that the operating environment is within specified operating limits.
CO2 reading is too high. Source of CO2 near the transmitter.
  • Use a portable instrument to verify the CO2 reading at the installation location. Avoid breathing on the instruments while checking.
  • Check for sources of CO2 in the measured area, such as people working right next to the transmitter.
CO2 measurement module must be replaced. See Replacing the CO2 measurement module (GM10).
CO2 reading is too low. The measured area contains materials that bind CO2 (such as fresh concrete), producing a low-CO2 environment.
  • Use a portable instrument to verify the CO2 reading at the installation location. Avoid breathing on the instruments while checking.
  • Check if the transmitter is installed on a mounting box that supplies air from inside the wall into the transmitter. If yes, seal the opening that supplies the air.
CO2 measurement module must be replaced. See Replacing the CO2 measurement module (GM10).
Relay is always activated. Relay setpoint set too low. Adjust the relay setpoint. See Relay.

Error text on display:

CO2-SENSOR

GM10 module disconnected. Open the transmitter and check if the GM10 module is installed securely. See Figure 2.
  • If the module is loose or entirely disconnected, reinstall it as instructed in Replacing the CO2 measurement module (GM10).
  • If the GM10 module appears to be installed but the problem persists, disconnect and reconnect the module carefully.
CO2 measurement module must be replaced. Replace the GM10 module with a verified working module.
CO2 reading over 6000 ppm.
  • Use a portable instrument to verify the CO2 reading at the installation location. Avoid breathing on the instruments while checking.
  • Check for sources of CO2 in the measured area, such as people working right next to the transmitter.

Error text on display:

RH-SENSOR

Humidity sensor disconnected. Open the transmitter and check the condition of the humidity sensor. See Figure 2.
Humidity sensor damaged.
Humidity sensor wet.

Error text on display:

T-SENSOR

Temperature reading is outside the scaled output range.
Temperature sensor damaged. Open the transmitter and check if the active temperature sensor on the component board has been damaged. See Figure 2.

Error text on display:

INTERNAL

Problem with transmitter software.
  • Restart the transmitter.
  • If the error persists, contact Vaisala support.
Table 2. Troubleshooting table, transmitter model GMW87
Problem Solution
The device is not responding
  • Power-cycle the transmitter by disconnecting the screw terminal block
  • Check power supply voltage
  • Check wiring, including RS-485 bus polarity
  • Check that RS GND is connected between the transmitter and the receiver
  • Compare the DIP switch settings to your Modbus host settings
  • Check that RS-485 termination is enabled only on the last device of the wiring
  • Alternatively, try operation without RS-485 termination at all
Unexpected value in Modbus response
  • Change register number and/or data encoding settings in your Modbus host system
No measurement result and/or non-zero status code returned
  • Device is warming up, try again after 20 seconds
  • Power-cycle the transmitter by disconnecting the screw terminal block
  • Check that the GM10 module is properly attached
  • Contact Vaisala for a replacement GM10 module