If you experience problems with GMW80 series transmitters, first see the following tables (for analog output and Modbus models) concerning the behavior and error indications of the transmitter. If you cannot locate the source of the error and return the transmitter to operational state, contact Vaisala. See Technical support.
Problem or message | Possible cause | Solution |
---|---|---|
Analog output reading is unchanging and appears incorrect. | Transmitter has set the analog output to the error level (3.6 mA or 11 V) because the transmitter is in the error state. |
Determine what has caused the error state and remove the cause. For a description of the error state and its possible causes, see Error state. |
Temperature reading is too high. | Transmitter is installed in an unsuitable location, for example, near a heat source or in sunlight. | Relocate transmitter. See Selecting location. |
Transmitter is installed in improper orientation. | Reinstall transmitter with the arrow on the mounting base pointing up. | |
Unsuitable operating environment. | Verify that the operating environment is within specified operating limits. | |
CO2 reading is too high. | Source of CO2 near the transmitter. |
|
CO2 measurement module must be replaced. | See Replacing the CO2 measurement module (GM10). | |
CO2 reading is too low. | The measured area contains materials that bind CO2 (such as fresh concrete), producing a low-CO2 environment. |
|
CO2 measurement module must be replaced. | See Replacing the CO2 measurement module (GM10). | |
Relay is always activated. | Relay setpoint set too low. | Adjust the relay setpoint. See Relay. |
Error text on display: CO2-SENSOR |
GM10 module disconnected. | Open the transmitter and check if the GM10 module is installed securely. See Figure 2.
|
CO2 measurement module must be replaced. | Replace the GM10 module with a verified working module. | |
CO2 reading over 6000 ppm. |
|
|
Error text on display: RH-SENSOR |
Humidity sensor disconnected. | Open the transmitter and check the condition of the humidity sensor. See Figure 2.
|
Humidity sensor damaged. | ||
Humidity sensor wet. | ||
Error text on display: T-SENSOR |
Temperature reading is outside the scaled output range. |
|
Temperature sensor damaged. | Open the transmitter and check if the active temperature sensor on the component board has been damaged. See Figure 2. | |
Error text on display: INTERNAL |
Problem with transmitter software. |
|
Problem | Solution |
---|---|
The device is not responding |
|
Unexpected value in Modbus response |
|
No measurement result and/or non-zero status code returned |
|