Modbus registers - GMW83 - GMW83A - GMW83D - GMW83DRP - GMW83DRPC - GMW83RPC - GMW84 - GMW84S - GMW86P - GMW87M

GMW80 Series User Guide

Document code
M211748EN
Revision
H
Language
English
Product
GMW83
GMW83A
GMW83D
GMW83DRP
GMW83DRPC
GMW83RPC
GMW84
GMW84S
GMW86P
GMW87M
Document type
User guide
CAUTION Registers are numbered in decimal, starting from 1. Register addresses in actual Modbus messages (Modbus Protocol Data Unit (PDU)) are in hexadecimal and start from zero. Subtract 1 from the register number presented in this manual to get the address used in the Modbus message (for example, register number 1 corresponds to address 0hex in the actual Modbus message).

Accessing unavailable (temporarily missing) measurement data does not generate a Modbus exception. “Unavailable” value (a quiet NaN for floating point data or 8000hex for integer data) is returned instead. An exception is generated only for any access outside the applicable register ranges.