Analog outputs of the HMDW100 series transmitters have a defined behavior when the values measured by the transmitter are outside the scaled analog output range:

  • Output is clipped at the end of the scaled output range.
  • You can allow the output to exceed the scaled range by 10 % with the aover serial command.
  • Output is set to error state (default 3.6 mA) if an error is active (for example, due to sensor damage). You can change the error state using the aerr command.

For configuration of the analog outputs using serial commands, see Analog output.