SR50A cable wiring - RWS200

RWS200 Installation Manual

Product status
Document code
M211608EN
Revision
AA
ft:locale
en-US
Product
RWS200
Document type
User guide
SR50A cables
Cable code Cable length Number of wires PMU701 slot
SR50ACBL-10M 10 m (32 ft 10 in) 5 + shield 1 E1 (first sensor)
SR50ACBL-30M 30 m (98 ft 5 in) E2 (second sensor)
SR50ACBL-100M 100 m (328 ft 1 in)
SR50A cable termination to 10‑pin connector
Signal Wire color PMU701 connector pin Wire color Signal
Not connected 10 5 Not connected
Not connected 9 4 Not connected
Not connected 8 3 Not connected
Power in +12 V Red 7 2 Green RS-485 D−
Shield and ground for power Clear and black 6 1 White RS-485 D+
SR50A cable shield
Color Usage Action
Shield Ground

Connect to PMU701 sensor grounding rail.

SR50A wiring
1 Calculated after cutting the cable.