The following figure shows the default wiring of the relays to the PMU701 POWEROUT connector and to the DMU703 DIGITAL connector.Relay wiring to DMU703The following figure shows how to connect the relays so that when one of the relays activates, the other relays is never activated. In this case, route power through Relay 3 to the other relays. In error situations, Relay 3 activates and cuts power from the other relays.Wiring power through one of the
relaysThe following figure shows how to connect a failsafe device that switches on with normally closed contacts. Configure inverted activation logic for the relay.Fail-safe device with normally closed
contactsThe following figure shows how to connect a failsafe device that switches on with normally open contacts. Configure inverted activation logic for the relay.Fail-safe device with normally open
contacts