Grounding weather station enclosure - RWS200

RWS200 Installation Manual

Product status
Document code
M211608EN
Revision
AA
ft:locale
en-US
Product
RWS200
Document type
User guide
WARNING Consult local electricity professionals for the local and state legislation and regulations about grounding.
WARNING Ground the product and verify outdoor installation grounding periodically. Failure to provide proper grounding can result in injury or death from electrical shock and can severely damage the equipment.
WARNING A long cable between units (sensors, transmitters, power supplies, and displays) can cause a lethal lightning-induced current surge. Always ground the enclosure to a suitable grounded location with a short, low-resistance cable.
WARNING Lightning protection is required to prevent injury and damage to equipment due to direct lightning strikes and lightning-induced current surges.

Make sure that the mast is protected from lightning strikes. See Grounding and Lightning Protection in Vaisala Outdoor Installations Technical Reference (M211786EN).

Inside the weather station enclosure, PMU701 is grounded to the enclosure, and sensors are grounded to the PMU701 grounding rail for sensor cables or the enclosure grounding rail for sensor cables.

You need a separate grounding cable to ground the weather station enclosure.

  1. Connect the grounding cable to the grounding point underneath the weather station enclosure.
    1
    System grounding point
    2
    Enclosure grounding cable
  2. If the weather station enclosure does not have a system grounding point underneath the enclosure, connect the grounding cable to the backplate grounding point. Lead the grounding wire through a conduit hole at the bottom of the enclosure.
    1
    AC (mains) cable
    2
    Backplate grounding point
    3
    Cable lug with hole Ø 6.2 mm (0.24 in)
  3. Connect the other end of the cable to a grounded location, such as grounding connector.