Adding wire-end ferrules - RWS200

RWS200 Installation Manual

Product status
Document code
M211608EN
Revision
AA
ft:locale
en-US
Product
RWS200
Document type
User guide
  • Cable strippers
  • Crimping tool
WARNING Make sure that you prepare or connect only de-energized wires.
  1. Strip the wires that are going to be connected.

    Strip a piece that is 1 mm (0.04 in) longer than the ferrule.

    For details on the wiring, see:

    • Wiring instructions for the sensor
    • Quick reference card for the sensor
    • Wiring diagrams
    Check that the number and color of unused wires match the number and color listed in the quick reference cards. If not, the cable is not correct.
  2. Crimp the ferrules to the wires.
    Use a professional crimping tool and press hard enough to make sure that the ferrule holds fast.
    To make sure that the contact is good, use 10‑mm (0.39‑in) ferrules.
    1

    Ferrule (10 mm / 0.39 in)

    2
    Unused wires covered with a shrinkable tube or electrical tape
    3

    Cut the wires to approximately 15 cm (6 in) in length (cables to PMU701), 20 cm (8 in) (cables to DRI701), 40 cm (16 in) (WMT700 with transducer and arms heating)

    4
    Cable shield folded over cable jacket
    5
    Cable
  3. Cut unused wires to different lengths and tie them together with electrical tape.
    CAUTION If exposed wires come in contact with the shield, ground, or each other, they can interfere with signals from other sensors on the same line. Cut unused wires to different lengths and insulate them with electrical tape. Avoid cutting the wires too short.