Connections - WAC155

WAC155 User Guide

Document code
M210822EN
Revision
F
Language
English
Product
WAC155
Document type
User guide

WAC155 provides the line cable entry through a gland for a cable with a diameter 7 ... 10 mm. For better protection against RF interference, bend the cable shield.

Figure 1. Braided cable shield

WAC155 has 3 plug-in I/O connectors: X1, X2, and X3. The terminals accept wires with maximum cross-section area of 1.5 mm2.

Figure 2. I/O connectors

For the location of the connectors and the cable routing through the cable glands, see Sensor Wiring.

The following tables show the I/O connector pinouts.

Table 1. Anemometer connector (X1) pinout
Pin number Signal Description
1 F Frequency input from sensor
2 F+ Supply voltage output to sensor
3 GND Sensor ground
4 HT1 Heating supply through control switch from X2
5 HTC Heating common for heater serial connection
Table 2. Power/Control connector (X2) pinout
Pin number Signal Description
1 HT1+ Heating supply input (+)
2 HT2- Heating supply input (-)
3 Vin+ Supply voltage input
4 Vin+ Supply voltage input
5 Vin- Supply voltage ground
6 Vin- Supply voltage ground
7 SD1- RS-485 inverting I/O
8 SD1+ RS-485 non-inverting I/O
Table 3. Wind direction sensor connector (X3) pinout
Pin number Signal Description
1 HTC Heating common for heater serial connection
2 HT2 Heating supply return to connector X2
3 GND Sensor ground
4 D+ Supply voltage output to sensor
5 G5 Gray code input from sensor, bit 5
6 G4 Gray code input from sensor, bit 4
7 G3 Gray code input from sensor, bit 3
8 G2 Gray code input from sensor, bit 2
9 G1 Gray code input from sensor, bit 1
10 G0 Gray code input from sensor, bit 0
11 AIP+ Reserved for analog vane