| Property | Description/Value |
|---|---|
| Input voltage 1 |
Power channels: max. ±43 V Data channels: max. ±13 V |
| Input common mode voltage | Any line to earth: max. ±72 V |
| Throughput current |
Power lines: max. 1.5 A Data lines: max. 0.16 A |
| Throughput resistance (per line) |
Power lines: max. 0.3 Ω Data lines: max. 15 Ω |
| Turn-on voltage |
Power channels: max. ±60 V Data channels: max. ±16 V |
| Surge current |
To earth: max. 10 kA Differential: max. 5 kA |
| Property | Description/Value |
|---|---|
| Weight | 0.65 kg (1.43 lb) |
| Housing material | Polycarbonate, stainless steel |
| Housing dimensions (H × W × D) | 94 × 130 × 58 mm (3.70 × 5.12 × 2.28 in) |
| Dimensions with cable glands and mounting assembly (H × W × D) | 112 × 130 × 69 mm (4.41 × 5.12 × 2.72 in) |
| Cables (Ø) | 5 … 10 mm (0.20 … 0.39 in) |
| Wires (Ø) | 0.4 … 1.7 mm (0.016 … 0.067 in) (AWG 26 … 14) |
| Property | Description/Value |
|---|---|
| Operating temperature | -52 … +70 °C (-60 … +158 °F) |
| Storage temperature | -52 … +70 °C (-60 … +158 °F) |
| Installation temperature | -40 … +70 °C (-40 … +158 °F) |
| Maintenance work temperature | -40 … +70 °C (-40 … +158 °F) |
| Property | Description/Value |
|---|---|
| EMC surge tolerance |
EN 61000-4-5 (4 kV, 2 kA) IEEE C62.45 (6 kV, 3 kA) |
| IP rating | IP66 (NEMA 4X) |
1 Across channel line pair and
from line to GND, terminals #3