| Property | Description / Value |
|---|---|
| Operating temperature | −40 … +60 °C (−40 … +140 °F) |
| Property | Description / Value |
|---|---|
| Line types |
AC (mains) 115/230 VAC Signal lines |
| Signal line types |
Modem line (leased) 2-wire RS-485 RS-232C Local operating network (LON) |
| Mains in connector |
Number of contacts: 5 (L1, L2, L3, N, PE) Contact area: 10 mm2 |
| Mains out connectors |
Number of contacts: 2 × 3 (L, N, PE) Contact area: 10 mm2 |
| Signal line connectors |
Integrated to signal line protectors 2.5 mm2 Contact area: 2.5 mm2 |
| Grounding cable clamp | For 16 mm2 jacketed cable |
| Cable glands |
The shield can be grounded to the following sizes of cable glands:
|
| AC (mains) 115/230 VAC in |
1 × Ø 18 ... 25 mm (0.71 ... 0.98 in) |
| AC (mains) 115/230 VAC out |
1 × Ø 18 ... 25 mm (0.71 ... 0.98 in) and 2 × Ø 7 ... 12 mm (0.28 ... 0.47 in) |
| Signal line in | 1 × Ø 7 ... 12 mm (0.28 ... 0.47 in) (TERMBOX‑1212: 2 pcs) |
| Signal line out | 1 × Ø 5 ... 10 mm (0.20 ... 0.39 in) (TERMBOX‑1212: 2 pcs) |
| Property | Description / Value |
|---|---|
| Safety | IEC / EN60950 |
| Property | Description / Value |
|---|---|
| Input voltage range | 100 ... 240 VAC, −10 % ... +6 % |
| Irms | Maximum 10 A |
| Phoenix Plugtrap VAL‑SEC‑T2‑1S‑350‑FM1 | IEC category IIEN type T2 |
| Imax (8/20 μs) | 15 kA |
| Protection level | 1500 VDC at 10 kA |
| Property | Description / Value |
|---|---|
| Protection component |
Phoenix Contact PT 1x2-BE base element (rail-mountable) Phoenix Contact PT 3-HF-12DC-ST plug Base element PT 1x2+F-BE |
| Imax (8/20 μs) | 10 kA |
| Protection level (1kV/1μs) | 25 V |
| Serial resistance | 2.2 Ω |
| Property | Description / Value |
|---|---|
| Bandwidth | 70 MHz |
| Property | Description / Value |
|---|---|
| IP rating | IP66 |
| Dimensions (W × D × H) | 260 × 160 × 91 mm (10.24 × 6.30 × 3.58 in) |
| Color | RAL 9003 |
| Weight | 3.1 kg (6.8 lb) |
1 For 230 VAC networks. Also suitable
for 115 VAC networks.