Feature | Specification |
---|---|
Cable |
IEC 61158‑2 compliant 2-wire cable: 2 signal wires and shield copper area 0.8 mm2 (18 AWG) cable resistance 24 Ω/km (per wire) cable attenuation 3.0 dB/km at 28 kHz |
Cable length |
Standard 10 m (33 ft), max. total length 200 m (660 ft) |
For information on the intrinsically safe cabling for PR‑23‑…‑IA/‑CI, see Intrinsically safe mounting. |