Intrisincally safe mounting - PR-21-S

PR-21 Series User Guide

Document code
IM-EN-PR21S
Revision
C
Language
English
Product
PR-21-S
Document type
User guide

Choose the mounting location of the sensor, the isolator/barrier unit and the indicating transmitter so that they are protected from sudden impact and friction.

The electrical connections for PR‑21‑S‑…‑IA are described in the following figure.

Figure 1. Intrinsically safe wiring, PR‑21‑S‑…‑IA

Cables:

  • 10 m (33 ft) cable, part number PR‑8230‑010, connecting the Indicating transmitter STR and the Isolator unit. The maximum cable length is 100 m (330 ft).
  • 10 m (33 ft) power cable, part number PR‑8250‑010, connecting the Indicating transmitter STR and the Isolator unit, part number PR‑8250‑010. The maximum length is 100 m (330 ft).
  • The intrinsically safe cable between Isolator unit and sensor, part PR‑8260‑xxx, where xxx is the cable length in meters. The maximum length is 100 m (330 ft). For cable connections, see Figure 1 and Figure 1.
Isolator/Barrier Unit can also use an optional external +24 V DC power supply instead of the +24 V DC power supply from the transmitter. +24 V DC is connected to terminals 13 and 14. If +24 V DC is used, the PR‑8250 power cable is not used at all.