All the electrical terminals of the indicating transmitter are behind the front panel. To access them, first open the enclosure cover. Then loosen the front panel screw in the figure below, and swing open the front panel. All terminals are now accessible.
Make sure that you mount an external power switch for the divert control unit that is close to the unit and easily reachable. Make sure that you mark it as a disconnecting device. The following figure shows the recommended external power switch, spare part nr PR‑10900. The ratings of the switch are 10 A and 250 V.
The following table describes the terminals on the H1 interface card PR‑10701 and on the transmitter motherboard PR‑10600.
Terminal | Usage | ||
---|---|---|---|
On H1 | |||
A 1 2 3 | Connection for Sensor A, signal wires (1, 2), cable shield (3). | ||
B 1 2 3 | Connection for Sensor B, signal wires (1, 2), cable shield (3). | ||
On motherboard | |||
11 12 | 4 … 20 mA output 1, positive (11), negative (12), max. load 1000 Ω, galvanically isolated. | ||
13 14 | 4 … 20 mA output 2, positive (13), negative (14), max. load 1000 Ω, galvanically isolated. | ||
21 221 | Relay 1, one contact output, max. 240 V AC, max. 3 A, fuse with voltage 250 V AC, max fuse size 3 A, speed slow. | ||
23 241 | Relay 2, one contact output, max. 240 V AC, max. 3 A, fuse with voltage 250 V AC, max fuse size 3 A, speed slow. | ||
31 32 331 |
Power, L (31), N (32), protective earth (33), 100 … 240 V AC, 50 … 60 Hz, fuse with voltage 250 V AC, max. size 10 A and speed slow. An external power switch is mandatory. Power, + (31), - (32), protective earth (33), 24 V DC ± 10%, fuse with voltage min 48 V DC, max. size 4 A and speed fast. |
||
41 42 | 24 V terminal for DTR internal use only.
|
||
51 52 53 54 55 | Switch inputs: switch 1 (51), switch 2 (52), switch 3 (53), switch 4 (54) and common 3 V for all inputs (55). The switch terminals are galvanically isolated. |