mA output module PR-50021 - PR-43-AC - PR-43-AP - PR-43-GC - PR-43-GP - PR-43-PC

MI User Guide

Document code
IM-EN-MI
Revision
D
Language
English
Product
PR-43-AC
PR-43-AP
PR-43-GC
PR-43-GP
PR-43-PC
Document type
User guide

The mA output module card adds mA outputs to Multichannel User Interface MI. On the module card there are 2 independent 4 … 20 mA current sources. Both current outputs are configurable independently to indicate for example process concentration or temperature or other diagnostic data of any connected refractometer. A mA output has traceable calibration, accuracy is ±0.02 mA.

Maximum load (compliance) is 1000 Ω. There is a place inside the Multichannel User Interface MI where the cable shield can be connected for grounding.

Table 1. Cable specifications
Item Specification
Conductor cross section 0.14 … 1.5 mm2 (28 … 16 AWG)
Tightening torque 0.25 Nm (0.18 ft lbs)
Figure 1. mA output pinout

The mA outputs are compliant to Namur NE43. NAMUR NE 43 uses the 3.8 … 20.5 mA signal range for measurement information, with values ≥21 mA or ≤3.6 mA to indicate diagnostic failures. With that information, it is easier to detect a failure condition on a refractometer, for example, it clearly tells you if you have an empty pipe.

Figure 2. Default mA output values

Certain malfunctions cause the mA measurements to return to mA default output value, see the following table. Factory setting for default output value is 3.4 mA.

Table 2. Messages causing mA output value to return to default output
Message Returns to default mA
Conc Temp
Short-circuit
No optical image
Temp measurement fault
No sample
Prism coated
No connection