AP10 firmware version 5.0.0 - AP10

AP10 Firmware Release Notes

Document code
DOC246159
Revision
R
Language
English
Product
AP10
Document type
Release notes

Support for VaiNet network segments, also known as large VaiNet.

Release date: October 2023

New features and improvements

The ability to configure VaiNet segments (four segments; A, B, C, and D) to enable the setup of large VaiNet systems. Each segment can accommodate up to 256 loggers, using up to 8 APs. The maximum network size can support up to 1024 data loggers.

It is recommended to leave some unused connection capacity in each segment and not plan for a fully maxed out system. For more comprehensive planning guidance, see Guidelines for Large VaiNet Systems (M212596EN).

Fixes

The following bugs affecting the reliability of AP10 were fixed:

  • Fixed an infrequent issue which made the AP10 freeze and require a reboot after changing the VaiNet channel setting.
  • Corrected a significant clock time drift issue which could occur after device start up.
  • Fixed an issue that caused a 2 second time difference between AP10 time and RFL100.

Compatibility and upgradeability

  • Available as firmware update for any AP10 hardware revision G or H.
  • Not compatible with other AP10 devices in the same network with firmware older than version 5.0.0.
  • Compatible with RFL100 version 1.8.0 in all segments (A to D).
  • Compatible with RFL100 versions before version 1.8.0 provided they join segment A.